| Model | GBP48-280L | GBP48-314L | GBP48-560L | GBP48-628L | GBP512-280L | GBP51.2-314L | GBP51.2-560L | GBP512-628L |
| Nominal
Voltage (V) | 48 | 51.2 |
| Cell
Specification | 280 | 314 | 280 | 314 | 280 | 314 | 280 | 314 |
| Nominal
Capacity (Ah) | 280 | 314 | 560 | 628 | 280 | 314 | 560 | 628 |
| Operating
Voltage Range (V) | 42~54.75 | 44.8~58.4 |
| Recommended
Charging Voltage (V) | 51.75 | 55.2 |
| Recommended Discharge
Cut-off Voltage (V) | 45 | 48 |
| Standard Charge/
Discharge Current (A) | 100 | 100 | 100 | 100 |
| Maximum Continuous
Charge/Discharge
Current (A) | 150 | 200 | 150 | 200 |
| Operating
Temperature (C) | -30~60(Recommended 10~35) |
| Allowable Humidity
Range(%RH) | <85 |
| Storage
Temperature(C) | -20~65(Recommended 10~35) |
| Charging Temperature(C) | 0~55 |
| Discharging
Temperature(C) | 1-10~55 |
| Protection Level | IP20 |
| Cooling Method | Natural Air Cooling |
| Cycle Life | 5000+ Times at 80% DOD |
| Maximum Dimension (D*W*H)mm | 248*680*880 | 890*350*1060 | 248*680*880 | 890*350*1060 |
| Weight(kg) | 137 | 141 | 280 | 289 | 139 | 144 | 284/293 |
| Note: The above data is for reference only. in case of any changes, no further notice will be given.
For special customization requirements, please consult with the engineer. |