- +(86) 514-87520588
- norah@gsopower.com
| Model | GSO50-100/GSO125-245 |
| Style | Out Door Cabinet-On/off Grid |
| Cell | REPT、EVE、etc |
| Cycle | 6000+ times |
| Life | 10 years |
| Certificate | CE 、UL、MSDS、UN38.3 |
| Model | GSO50-100 | GSO80-165 | GSO105-200 | GSO105-225 | GSO125-245 | ||
| On grid parameter | Rated power(kW) | 50 | 80 | 105 | 125 | ||
| Maximum output power(kW) | 55 | 88 | 116 | 138 | |||
| Rated grid voltage(V) | 400 | ||||||
| Rated current(A) | 72 | 115 | 167 | 200 | |||
| Allowable grid voltage(V) | ±15% | ||||||
| Rated grid frequency(Hz) | 50±5 | ||||||
| Power Factor | 0.99 | ||||||
| THDI | <3%(Rated power) | ||||||
| Overload capacity | 110% Long term | ||||||
| Access method | 3P4W | ||||||
| Off grid parameter | Rated output voltage(V) | 400 | |||||
| Rated output power(kW) | 50 | 80 | 100 | 125 | |||
| Rated grid frequency(Hz) | 50±5 | ||||||
| THDU | <3%(Linear power) | ||||||
| Unbalanced load capacity | 100% | ||||||
| Overload capacity | 110% Long term | ||||||
| Charge and discharge conversion time (ms) | <20 | ||||||
| Battery parameter | Battery system configuration | 1P216S | 1P224S | 1P224S | 1P224S | 1P238S | |
| Cell Type | 150Ah | 230Ah | 280Ah | 314Ah | 320Ah | ||
| Rated voltage(V) | 691.2 | 716.8 | 716.8 | 716.8 | 761.6 | ||
| Operating voltage(V) | 672~767 | 672~796 | 672~796 | 672~796 | 672~845 | ||
| Battery Capacity(kWh) | 108 | 170 | 215 | 230 | 255 | ||
| PV | PV voltage range | 500~620 | 500~620 | 500~620 | 500~620 | 500~660 | |
| Maximum input power(kW) | 50 | 100 | |||||
| Rated current on Low voltage side(A) | 100 | 200 | |||||
| Maximum efficiency | ≥99% | ||||||
| Number of MPPT tracker | 1 | 2 | |||||
| System efficiency | PCS maximum efficiency | ≥98% | |||||
| System maximum efficiency | >90% | ||||||
| Battery charge and discharge rate | ≤0.5C | ||||||
| Protection | Battery reverse connection protection | Yes | |||||
| DC overcurrent protection | Yes | ||||||
| AC overcurrent protection | Yes | ||||||
| AC overvoltage protection | Yes | ||||||
| Surge protection | Yes | ||||||
| Fire protection system | Non-stationary pressure perfluoroacetone | ||||||
| Grid support | L/HVRT, active and reactive power control | ||||||
| General parameter | Dimensions(D*W*H)mm | 1400*1400*2200 | 1400*1950*2200 | ||||
| Weight (t) | 2.5 | 3 | 3.3 | 3.7 | 4 | ||
| Line entry method | Side entry | ||||||
| Ambient temperature(℃) | -20~50( De-rating power from 45℃) | ||||||
| Charging temperature(℃) | 0~55 | ||||||
| Discharge temperature(℃) | -10~55 | ||||||
| Ambient humidity(%RH) | <95%RH,non-condensing | ||||||
| Working altitude(m) | 5000(De-rating power from 2000m) | ||||||
| Ingress Protection Rating | IP54(IP65 for key components) | ||||||
| Cooling method | Industrial air conditioning (battery compartment) / forced air cooling (electrical compartment) | ||||||
| Commu- nication | Communication interface | CAN/RS485/Ethernet | |||||
| Communication Protocol | RTU/MODBUS-TCP | ||||||